Function Group 9 – Analog Input Signal Operation
Function
No. Description Range/Code
Factory
Setting
User
Setting
9.00 Analog Input 1 Gain (%) 0 – 500 100
9.01 Analog Input 1 Slope
0000: Positive
0001: Negative
0000
9.02 Analog Input 1 Offset (%) 0 – 100 0
9.03 Analog Input 1 Type
0000: Unidirectional
(1)
0001: Bidirectional
0002: PWM
(2)
0000
9.04 Analog Input 1 Response Time (mSec) 2 – 10 2
9.05 Analog Input 2 Gain (%)
(3)
0 – 500 100
9.06 Analog Input 2 Slope
(3)
0000: Positive
0001: Negative
0000
9.07 Analog Input 2 Offset (%)
(3)
0 – 100 0
9.08
Analog Input 2 Response Time
(mSec)
(3)
2 – 10 2
Notes: (1) Can be used for Current Signal input, by setting Jumper J2, on the drive, to the
"CUR" position. (2) 0.15 – 1 kHz (0 – 100% duty cycle). (3) IODF Option Board required.